- The underfloor heating pipe clips should be spaced 1 meter apart. The pipes can also be tied to meshing layered on top of the insulation
Back to list
Top DIY heating plumbing tips 1
- Each pipe loop comes in 100 meter maximum coil length which is marked every meter so enabling you to check the length of each loop
- The 100 meter maximum coil length is linked to the head pressure from the pump which is only capable of pressurizing water through 100 meters of pipe
- 100 meters of MLC pipe covers approximately 25m2, but don't forget to take into account the length of the flow and return feeder pipes from the manifolds to each room
Back to list
Top DIY heating plumbing tips 1
- For new well insulated homes a spacing of 300mm (pipe center to pipe center) is recommended. For existing and older homes that are not well insulated then 200mm spacing should be used
- You should always try to use the 100 meter of pipe whatever the size room rather than cutting the pipe, e.g, 300mm spacing in a room sized 23m2 and 200mm spacing in a room sized 15m2 as this would be a cost effective way of using MLC pipe. In the larger room the water flow rate can be adjusted to compensate for the wider pipe spacing. The 200mm spacing in the smaller room translates into a faster heating
Back to list
Top DIY heating plumbing tips 1
- The pipe should be laid in accordance to heat output importance which is simply:
- Cold spots first like external walls
- Internal walls second
Back to list
Top DIY heating plumbing tips 1
- The pipe should be 100mm from the external wall
- Areas of full length glazing can benefit with a few rows of 100mm spacing to off-set the increased heat loss from those areas of floor to ceiling glazing
Back to list
- The Flow temperature can vary between 35 and 60oC depending on your building heat loss and flooring type. The flow temperature (for underfloor heating systems using thermostatic mixing valves) for screed floors should be about 43oC and 55oC for timber/timber suspended and floating floors
- The temperature difference between the flow and return pipes can range from 5 to 10oC
Back to list
Top DIY heating plumbing tips 1
- The Manifold distributes the heated water to each room. The flow rate is controlled by the flow gauge on the flow pipe which can be adjusted manually (normally full flow rate is used with 100 meter pipe and half the flow rate if 50 meter or pipe is used)
- If you wanted individual room control, thermostatic actuators wired to the room timers can be fitted to the return manifold.
Back to list
Top DIY heating plumbing tips 1
- The system is filled by using mains water pressure and vented (purged) of air
- This is done through the end caps on the manifolds.
- All the circuit valves on the manifolds should be closed
- The flow end cap should be connected by a hose to the water main
- The hose connected to the return end cap should be placed in a bucket by an external drain (the use of the bucket will enable you to see when the system is free of air as air bubbles will easily be seen)
- Then one by one the flow and return valves are opened, the circuit purged of air and closed
- Purge flow and return manifolds and close off, closing the return manifold first, then the flow manifold, and finally the water main outlet
Back to list
Top DIY heating plumbing tips 1
- The system should be tested before the screed and floor is laid at an air pressure of 6 bar (600kpa) for 24 hours. You are looking for air leaks which you will detect by a fall in pressure.
Back to list
Top DIY heating plumbing tips 1
- Apart from the manifolds and the underfloor pipe there is:
- A 2 port motorized valve
- A Pump
- A 3 or 4 port mixing valve
- A Programmable room thermostat - and individual room timers if needed
Back to list
Top DIY heating plumbing tips 1
- For floor areas up to 250 square meter use a pump that can deliver a 60 kpa head pressure, and for floor areas larger than 250 square meter use a pump with 80 kpa head pressure
Top Of DIY Heating Plumbing Tips 1 Page
Return To DIY Heating Plumbing Tips Page